This building-automation lab connects a Linux client and one controller through the same local network.
Open the controller properties to inspect its selected profile, device identity and live objects; an object instance identifies one object on that device.
Give the controller a clear device name and a unique address on this network, keeping the client and controller in the same subnet.
Save the changes and reopen properties to confirm the new name and address; this form does not edit object definitions or live values.
From the Linux client, first ping the updated controller address to verify basic network connectivity.
Run the discovery command to list responding controllers; the result includes the device instance and its network address.
Repeat discovery with the controller’s device instance to narrow the results to that one device.
Read the device object name and compare it with the name you saved in properties.
Read the analog input’s present value and its units separately; the temperature value and its Celsius units are shown here.
Refresh values in properties and compare the temperature with the value returned by the client.
An object that does not exist returns an error; a second read of the valid object confirms the working path.
Power off the controller and repeat discovery and the property read; an unavailable device cannot return a successful value.
Power the controller on again, then verify that discovery and the valid property read both recover.
Reopen the saved lab to confirm its device name and address; this example covers one local network, with discovery between subnets left for a separate walkthrough.